POWER RATING | PRIME POWER | STANDBY POWER | |
Power | KVA | 180 | 200 |
KW | 144 | 160 | |
Rated Speed | r.p.m | 1500 | |
Standard Voltage | V | 400/230 | |
Available Voltages | V | 400/230 - 230/132 - 230 V | |
Rated at power factor | Cos Phi | 0.8 |
ENGINE | PRIME | STANDBY | |||
Rated Output | KW | 163 | 180 | ||
Manufacturer | Cummins | ||||
Model | 6CTA8.3-G1 | ||||
No. of Cylindirs and Build | 4 Cycle; In-line; 6 Cylinder Diesel | ||||
Aspiration and Cooling | Turbocharged, after-cooled | ||||
Bore/Stroke | mm | 114X135 | |||
Compress the ratio | 16.5:1 | ||||
Cooling system | Water-cooled | ||||
Engine Speed/Frequency | rpm/Hz | 1500/50HZ | |||
Coolant Capacity | L | 38 | |||
Starting System | Electric 24 volt DC | ||||
Displacement | L | 8.3 | |||
Lubricant system Capacity | L | 24 | |||
Battery Volatge / Capacity | 24VDC | ||||
Governing Type | Type | Mechanical | |||
Air Filter | Type | Dry | |||
Fuel Consumption | Load | 100% | 75% | 50% | 25% |
L/H | 40.0 | 30.0 | 20.0 | 11. |
ALTERNATOR BRAND | STAMFORD | LEROY SOMER | XINYABO | |
Model | UCI274C | LSA44.3S5 | SLG-144 | |
Exciter System | Self-excited, brushless | |||
Poles | Numbers | 4 | ||
Connection Type | Reconnectable | |||
Insulation Type | Class | Class H | ||
Voltage Regulator | A.V.R. (Electronic) | |||
Steady Voltage Precision | ± 1% | |||
Underspeed Protection | Standard | |||
Overexcitation Protection | IP23 | |||
TIF (1960 Weightings) | <50 |
Standard supply:
1) Powered by heavy duty industrial diesel engines, famous engine brand can be chosen.
2) Brushless alternator,single bearing,flange connection,IP23,H insulation class,with AVR.
3) Auto control panel with LCD display.
4) Engine mounted battery-charging alternator,Genset with battery charge of main supply.
5) Circuit Breaker,Exhaust Silencer.
6) Copper Radiator for 40°C ambient temperature and double-deck cooling,with fan guard and front guard.
7) Anti-vibration pads fixed between engine/alternator and base frame to ensure the compete genset running stable.
8) Skid-mounted bottom 8 hours fuel tank.
9) Extemal recessed emergency stop button for extra safety.
10)Optional:Soundproof,ATS(automatic transfer switch),AMF panel,Trailer,Parallel system.
Optional:
--Automatic Transfer Switch
--Soundproof Canopy
--Under base tank
--Oil filter
Diesel generator Specifications
1. Powered by reliable engines
2. Branded alternator
3. Open type, silent type or super silent type generator
4. ISO, CE certified
Generator specs:
Rated output: 2 to 2,000kW/2 to 2,500kVA
Rated voltage: L-N 110 to 277V, L-L 220 to 480V
Rated frequency: 50/60Hz
Cooling method: closed water-cooled or air-cooled
Starting method: electric start or recoil start
Rated speed: 1,500/1,800/3,000/3,600rpm
Noise level: 56 to 75dB, 7 meters away
Alternator:
Brands: Stamford, Leroy Somer, Mecc Alte and Keypower brushless alternator
Rated output: 8 to 2,000kW/10 to 2,500kVA
Rated voltage: L-N 110 to 277V, L-L 220 to 480V
Rated frequency: 50/60Hz
Phase: 3-phase, 4-wire or 1-phase, 2-wire
Connection: y or other type connection
Rated speed: 1,500/1,800rpm
Excitation: harmonic excitation or phase compound or brushless
Voltage regulation: AVR automatic
1.0% voltage regulation in static conditions (maximum)
Protection class: IP23
Control panel: Deepsea, ComAp
The panel is provided with:
Standard engine instrumentation
Voltmeter with selector switch
Ammeter with selector switch
Frequency meter
Current transformers
MCB of suitable rating with overload and short-circuit protection
Optional with AMF control panel or with ATS (automatic transfer switch)
Packing:
PE film with hard paper corner protector
AMF Control Panel- ComAp AMF20 Or DSE7320
Brand | Deepsea/ComAp |
The control module gives digital readouts of: Generator voltage; Output frequency; Engine speed; Battery voltage; Engine hours run. The control module has indicators for failure information: Overspeed/underspeed, Emergency stop Low oil pressure; High water temperature Failure to start Battery charger failure Automatic shutdown occurs under: Low engine oil pressure; High engine water temperature; Overspeed/underspeed; Failure to start after three attempts. |
FAQ(Frequently Asked Question): 1.What is your warranty period? Our payment terms is 1 year or 1000 running hours whichever comes first. But based on some special project, we can extended our warranty period. 2.Does your generator have global warranty? Yes, most of our products like Cummins, Perkins, Doosan power generator enjoy the global warranty service. And the alternator we use like Leroysomer, Stamford, marathon also enjoy the global warranty service, so you do not need to worry about the aftersales service. 3.Can you accept OEM? Yes, we can accept OEM. 4.What is your payment terms? We can accept T/T 30% in advance, and the balance 70% shall be paid before shipment or L/C at sight, L/C deferred payment terms or west union. 5.What is your delivery time? Our normal delivery time is 2 to 5 weeks. But if your order is some special engine and alternator, then the delivery time is longer. |