Customization: | Available |
---|---|
Type: | Self-Starting Diesel Generator |
Installation Method: | Fixed |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Diesel Engine Data | ||
Manufacturer: | YUCHAI Engine | |
Model: | YC4D75Z-D20 | |
Standby/Prime Power: | 60.5KW / 55KW | |
Rated Speed: | 1500(r/min) | |
Cycle: | 4 stroke | |
Cylinder Arrangement: | 4 in line | |
Displacement: | 4.214L | |
Bore and Stroke: | 108*115(mm) | |
Compression Ratio: | 17: 1 | |
Governor Type: | Mechanical | |
Start battery voltage: | 24V DC | |
Air Intake System | ||
Air Intake System: | Turbo | |
Min Intake Restriction: | 100kpa | |
Exhaust System | ||
Exhaust Temperature: | ≤650 ºC | |
Max Back Pressure: | 6kpa | |
Fuel System | ||
Fuel System: | Direct injection | |
100%( Prime Power) Load: | 200g/kwh | |
50%( Prime Power) Load: | 215g/kwh | |
Oil System | ||
Total Oil Capacity: | 11-13L | |
Oil Consumption: | ≤0.4g / kwh | |
Cooling System | ||
Cooling Way: | Water-cooled | |
Total Coolant Capacity: | 34L | |
Thermostat: | 76-86 ° C | |
Max Water Temperature: | 95 ° C | |
Alternator Data | ||
Manufacturer: | STARLIGHTSTAMFORD / SIEMENS / MARATHON / ENGGA / KEPU | |
Excitation Mode: | Brushless and self- exciting | |
Number of phase and Access Act: | 3-phase 4-wire | |
Connecting Type: | "Y" type connecting | |
Alternator Capacity: | 68.75KVA | |
Alternator Efficiencies: | 95% | |
Overload: | (PRP)110% load can run 1h | |
Protection Level: | IP22-IP23 | |
Insulation Class, Temperature Rise: | H / H | |
Telephone Influence Factor (TIF): | <50 | |
THF: | <2% | |
Voltage Regulation, Steady State: | ≤ ± 1% | |
Altitude: | ≤ 1000m | |
Genset Electrical Performance | |
Voltage Regulation: | ≥ ± 5% |
Voltage Regulation, Stead State: | ≤ ± 1% |
Sudden Voltage Warp (100% Sudden Reduce): | ≤ + 25% |
Sudden Voltage Warp (Sudden Increase): | ≤-20% |
Voltage Stable Time (100% Sudden Reduce): | ≤ 6S |
Voltage Stable Time (Sudden Increase): | ≤ 6S |
Frequency Regulation, Stead State: | ≤ 5% |
Frequency Waving: | ≤1.5% |
Sudden Frequency Warp (100% SuddenReduce): | ≤ + 12% |
Sudden Frequency Warp (Sudden Increase): | ≤-10% |
FrequencyRecoveryTime(100%SuddenReduce): | ≤ 5S |
FrequencyRecoveryTime(Sudden Increase): | ≤ 5S |
Options | ||||||
Engine | Alternator | |||||
Heater 2KW & 4KW | Anti Condensation Heater | |||||
Battery Charger 3.5A & 7A | Permanent Magnet Generator(PMG) | |||||
Water Separator | Drop CT(For Paralleling) | |||||
Daily Fuel Tank | ||||||
Fuel Level Sensor | ||||||
Control System | Others | |||||
Remote Control Panel | Rainproof Type | |||||
Auto Transfer Switch (ATS) | Soundproof Type | |||||
Paralleling System | Trailer Type | |||||
Open Type | ||||||
Overall Size | Weight | |||||
2000 (mm) * 780 (mm) * 1350 (mm) | 810(kg) | |||||
Soundproof Type | ||||||
Overall Size | Weight | |||||
2350 (mm) 1050 * (mm) * 1800 (mm) | 1150(kg) |
2) Brushless alternator,single bearing,flange connection,IP23,H insulation class,with AVR.
3) Auto control panel with LCD display.
4) Engine mounted battery-charging alternator,Genset with battery charge of main supply.
5) Circuit Breaker,Exhaust Silencer.
6) Copper Radiator for 40°C ambient temperature and double-deck cooling,with fan guard and front guard.
7) Anti-vibration pads fixed between engine/alternator and base frame to ensure the compete genset running stable.
8) Skid-mounted bottom 8 hours fuel tank.
9) Extemal recessed emergency stop button for extra safety.
10)Optional:Soundproof,ATS(automatic transfer switch),AMF panel,Trailer,Parallel system.
Optional:
--Automatic Transfer Switch
--Soundproof Canopy
--Under base tank
--Oil filter
Brand | Deepsea/ComAp |
The control module gives digital readouts of: Generator voltage; Output frequency; Engine speed; Battery voltage; Engine hours run. The control module has indicators for failure information: Overspeed/underspeed, Emergency stop Low oil pressure; High water temperature Failure to start Battery charger failure Automatic shutdown occurs under: Low engine oil pressure; High engine water temperature; Overspeed/underspeed; Failure to start after three attempts. |
FAQ(Frequently Asked Question): 1.What is your warranty period? Our payment terms is 1 year or 1000 running hours whichever comes first. But based on some special project, we can extended our warranty period. 2.Does your generator have global warranty? Yes, most of our products like Cummins, Perkins, Doosan power generator enjoy the global warranty service. And the alternator we use like Leroysomer, Stamford, marathon also enjoy the global warranty service, so you do not need to worry about the aftersales service. 3.Can you accept OEM? Yes, we can accept OEM. 4.What is your payment terms? We can accept T/T 30% in advance, and the balance 70% shall be paid before shipment or L/C at sight, L/C deferred payment terms or west union. 5.What is your delivery time? Our normal delivery time is 2 to 5 weeks. But if your order is some special engine and alternator, then the delivery time is longer. |
Contact information:
Ms. Hebe Wang