Customization: | Available |
---|---|
Type: | Self-Starting Diesel Generator |
Installation Method: | Fixed |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Diesel Generator Set Data | ||
Manufacturer: | XINYABO | |
Set Type: | GF2/3D-64 | |
Standby Output: | 64KW/80KVA | |
Prime Output: | 58KW/73KVA | |
Rated Current: | 105(A) | |
Rated Frequency: | 50(Hz) | |
Start-up time: | 5~6(s) | |
Power Factor: | 0.8(Lag) | |
Rated Voltage: | 400/230(V) |
Diesel Engine Data | |||||||||
Manufacturer: | DEUTZ | ||||||||
Model: | TD226B-4D | ||||||||
Standby Power: | 60KW | ||||||||
Rated Speed: | 1500(r/min) | ||||||||
Cycle: | 4 stroke | ||||||||
Cylinder Arrangement: | 4 in line | ||||||||
Displacement: | 4.16L | ||||||||
Bore and Stroke: | 105*120(mm) | ||||||||
Compression Ratio: | 16.0:1 | ||||||||
Governor Type: | Electronic | ||||||||
Start battery voltage: | 24V DC | ||||||||
Air Intake System | |||||||||
Air Intake System: | Turbo | ||||||||
Max Intake Restriction: | 5kpa | ||||||||
Burning Capacity: | 3.25m3/min | ||||||||
Air Flow: | 70m3/min | ||||||||
Exhaust System | |||||||||
Exhaust Gas Flow: | 7.6 m3/min | ||||||||
Exhaust Temperature: | 430ºC | ||||||||
Max Back Pressure: | 10kPa | ||||||||
Fuel System | |||||||||
Fuel System: | A model fuel pump | ||||||||
100%( Prime Power) Load: | 208g/kwh | ||||||||
50%( Prime Power) Load: | 223g/kwh | ||||||||
Oil System | |||||||||
Total Oil Capacity: | 9.5L | ||||||||
Oil Consumption: | ≤1.36g/kwh | ||||||||
Engine Oil Tank Capacity: | |||||||||
Oil Pressure at Rated RPM: | |||||||||
|
|||||||||
Cooling System | |||||||||
Cooling Way: | Water-cooled | ||||||||
Total Coolant Capacity: | 17L | ||||||||
Thermostat: | 95-105ºC | ||||||||
Max Water Temperature: | 104ºC | ||||||||
Alternator Data | |||||||||
Manufacturer: | XINYABO SLG224F-58 | ||||||||
Excitation Mode: | Brushless and self- exciting | ||||||||
Number of phase and Access Act: | 3-phase 4-wire | ||||||||
Connecting Type: | "Y" type connecting | ||||||||
Alternator Capacity: | 80KVA | ||||||||
Alternator Efficiencies: | 95% | ||||||||
Overload: | (PRP)110% load can run 1h | ||||||||
Protection Level: | IP22-IP23 | ||||||||
Insulation Class, Temperature Rise: | H/H | ||||||||
Telephone Influence Factor (TIF): | <50 | ||||||||
THF: | <2% | ||||||||
Voltage Regulation, Steady State: | ≤±1% | ||||||||
Air Cooling Flow: | 0.216m3/s | ||||||||
Altitude: | ≤1000m | ||||||||
Genset Electrical Performance | |||||||||
Voltage Regulation: | ≥±5% | ||||||||
Voltage Regulation, Stead State: | ≤±1% | ||||||||
Sudden Voltage Warp (100% Sudden Reduce): | ≤+25% | ||||||||
Sudden Voltage Warp (Sudden Increase): | ≤-20% | ||||||||
Voltage Stable Time (100% Sudden Reduce): | ≤6S | ||||||||
Voltage Stable Time (Sudden Increase): | ≤6S | ||||||||
Frequency Regulation, Stead State: | ≤5% | ||||||||
Frequency Waving: | ≤1.5% | ||||||||
Sudden Frequency Warp (100% SuddenReduce): | ≤+12% | ||||||||
Sudden Frequency Warp (Sudden Increase): | ≤-10% | ||||||||
FrequencyRecoveryTime(100%SuddenReduce): | ≤5S | ||||||||
FrequencyRecoveryTime(Sudden Increase): | ≤5S |
Model | Genset Parameters | Engine | Dimension | Net Weight |
Constant Output(KW/KVA) | Model | L*B*H (cm) |
(kg) | |
GF2/3D20 | 20 /25 | D226B-3D | 1800*850*1100 | 720 |
GF2/3D24 | 24 /30 | D226B-3D | 1800*850*1200 | 750 |
GF2/3D30 | 30 /37.5 | D226B-3D | 2000*900*1300 | 850 |
GF2/3D40 | 40 /50 | TD226B-3D | 2000*900*1300 | 900 |
GF2/3D50 | 50 /62.5 | TD226B-4D | 2200*960*1400 | 950 |
GF2/3D68 | 68 /85 | TD226B-6D | 2200*960*1400 | 1000 |
GF2/3D80 | 80 /100 | TD226B-6D | 2400*1060*1600 | 1250 |
GF2/3D100 | 100 /125 | TBD226B-6D | 2400*1060*1600 | 1400 |
GF2/3D120 | 120 /150 | TBD226B-6D5 | 2600*1060*1700 | 1450 |
GF2/3D160 | 160/200 | TBD234V6 | 271x113x171 | 2960 |
GF2/3D200 | 200/250 | TBD234V6 | 271x113x171 | 2960 |
GF2/3D250 | 250/312.5 | TBD234V6 | 302x113x171 | 3250 |
GF2/3D300 | 300/375 | TBD236V6 | 326x112x171 | 3400 |
GF2/3D360 | 360/450 | TBD234V6 | 417x132x202 | 4900 |
GF2/3D400 | 400/450 | TBD234V6 | 417x132x202 | 5300 |
GF2/3D500 | 500/625 | TBD604V6 | 453x151x216 | 5600 |
GF2/3D640 | 640/800 | TBD620V6 | 483x172x232 | 8270 |
GF2/3D750 | 750/940 | TBD620V6 | 483x172x232 | 8330 |
GF2/3D800 | 800/1000 | TBD620V6 | 483x172x232 | 8500 |
GF2/3D1000 | 1000/1250 | TBD620V6 | 531x172x232 | 10500 |
GF2/3D1100 | 1100/1375 | TBD620V6 | 531x172x232 | 10650 |
GF2/3D1200 | 1200/1500 | TBD620V6 | 541x172x232 | 10800 |
GF2/3D1500 | 1500/1875 | TBD620V6 | 604x172x232 | 13950 |
GF2/3D1700 | 1700/2125 | TBD620V6 | 609x172x232 | 14370 |
a) Diesel engine with all accessories, 3 filter, electric systems
b) Alternator
c) Steel structure
d) Fan and water tank cooling system
e) Flange connector
f) 12 / 24V starting motor and charge engine
g) Air cleaner, fuel cleaner, oil cleaner
h) On-board control panel
i) MCCB air conservation switch
j) 12 / 24V starting accumulator and Battery line
k) Set shock absorber
l) High-efficient silencer
Accessories:
1) Standard accessories: Common steel frame, circuit breaker, damper, exhaust silencer, flexible
pipe, battery and connecting wires, operation manual and document
2) Optional accessories: Engine coolant and oil heater, alternator space heater, cooling for heat
exchanger, control system with RS232/485, communication interface, battery charger by main
supply, daily fuel tank, ATS and paralleling system, soundproof canopy and moving trailer
AMF Control Panel- ComAp AMF20 Or DSE7320
Brand | Deepsea/ComAp |
The control module gives digital readouts of: Generator voltage; Output frequency; Engine speed; Battery voltage; Engine hours run. The control module has indicators for failure information: Overspeed/underspeed, Emergency stop Low oil pressure; High water temperature Failure to start Battery charger failure Automatic shutdown occurs under: Low engine oil pressure; High engine water temperature; Overspeed/underspeed; Failure to start after three attempts. |
FAQ(Frequently Asked Question): 1.What is your warranty period? Our payment terms is 1 year or 1000 running hours whichever comes first. But based on some special project, we can extended our warranty period. 2.Does your generator have global warranty? Yes, most of our products like Cummins, Doosan power generator enjoy the global warranty service. And the alternator we use like Leroysomer, Stamford, marathon also enjoy the global warranty service, so you do not need to worry about the aftersales service. 3.Can you accept OEM? Yes, we can accept OEM. 4.What is your payment terms? We can accept T/T 30% in advance, and the balance 70% shall be paid before shipment or L/C at sight, L/C deferred payment terms or west union. 5.What is your delivery time? Our normal delivery time is 2 to 5 weeks. But if your order is some special engine and alternator, then the delivery time is longer. |